Download

Eurosteamer GHS 600

Designation:GHS 600
Steam output:300 - 600 kg/h
Economiser:Possible
Dimensions:6,1 ˣ 2,5 ˣ 2,9 m
Installation in:Sea container
Transport weight:6000 kg
Medium:Saturated steam
Triggering overpressure SV:10 - 16 bar (or on request)
Boiler adjustment range:Pressure range: 4.5 - 14 bar
Max. operating pressure:ca. 14 bar
Fuel:Heating oil or natural gas
Natural gas connection:DN 40 / PN 16 depending on gas pressure
Safety equipment:EN 12953
Connection line: A / V:CEE 16A 5-pole / 400V
25 A protection
Flue system / height:Stainless steel chimney stack
Chimney stack height:6m or on request
Steam high pressure Flange:DN 50 / PN 40
Connection line:Up to 13 bar with hoses, from 16 bar only with fixed piping
Steam low pressure:
Cooler blow-down:Included
Water treatment:Softening in the container
Residual hardness monitoring:Optional
Feed water treatment:Partial degasing in the container
Pressure reduction station:0.2 - 10 bar optional
Frost protection device:If desired
Remote monitoring:Optional
Flexible connection line:As required
Dosing system:Included
Exterior colour:RAL 9002/9006 (alternative if desired)
Optional:
  • Connection accessories:
  • Oil tank
  • Osmosis system
  • Heat recovery
  • Condensate monitoring
  • Adaptation of the chimney height
Quality features:
  • Galvanised steel construction
  • Flexible sizes
  • Exterior colour can be selected
  • With noise reduction panels if desired
  • Exhaust gas and supply air noise suppressor